论文摘要

<正>The comprehensive sodium fire test to the scale of engineering application was carried out in the piping room of the integrated sodium fire safety facility (F204).The sodium in the temperature of 316℃was released into the piping room1 through the pipe breach in the flow rate of1.3 kg/s.The amount of leaked sodium reached200 kg after a duration of 150 s.The sodium burned rapidly in the tight piping room 1.The flow rate,temperature,pressure,and concentration of sodium aerosol war measured,and the performance of pressure relief device and special sodium aerosol detector were verified.

论文目录

文章来源

类型: 期刊论文

作者: DU Haiou,WANG Guozhi,SHI Wentao,PIAO Jun,WANG Rongdong

来源: Annual Report of China Institute of Atomic Energy 2019年00期

年度: 2019

分类: 工程科技Ⅱ辑

专业: 核科学技术

单位: Division of Reactor Engineering Technology Research

分类号: TL81

页码: 121-122

总页数: 2